(Click on schematic for large image)

 
 
 

US Patent 6,874,375

The Pitotless Nozzle is designed for taking precision flow rate measurements without a pitot. You'll never have to shut down in the middle of a test to change out a pitot because it got hit by a rock. Use the Pitotless Nozzle with the new Little Hose Monster™ or the 2 ½” Hose Monster® in fire pump testing, fire flow testing or unidirectional flushing; or mount it directly on a hydrant, test header valve, or any fixed 2 ½” outlet.

The standard hose connection is 2 ½” NH hard-coat anodized aluminum swivel coupling. We can provide just about any thread spec on request and we stock AMA, BCT, BSP, QST and WCT for quick turn around.

Flow rate is determined by reading internal pressure of the nozzle. With no pitot in the stream, most debris will pass through without causing damage. The unique and patented constant rate of area reduction shape of the Pitotless Nozzle creates a steady laminar flow. Even when attached directly to a hydrant nozzle, the gauge needle is steady.

  • No More Pitot Replacements
  • Read flows from 48 GPM to 1607 GPM
  • Four sizes - 1", 1 1/8", 1 3/4", 2"
  • Color-coded for easy size identification
  • FM Approved for flow rate accuracy
  • Creates a laminar flow that eliminates turbulence and gauge needle bounce
  • Anodized Aluminum
  • Use with the new Little Hose Monster™, the traditional Hose Monster™ or connect it directly to a test header or hydrant

If using the Pitotless Nozzle WITHOUT the Hose Monster.

The Pitotless Nozzle must be attached securely to a hydrant or other stationary device. The thrust created by high velocity water flow is dangerous to personnel and destructive to property. DO NOT attach the Pitotless Nozzle directly on the end of an unsecured hose. Clear water discharge path.

LIST OF “DO NOTS”

  • Do not attach the Pitotless Nozzle to the end of a hose unless the Little Hose Monster or Hose Monster is attached to it or unless it is permanently secured.
  • Do not attach a hose to the male outlet end of the Pitotless Nozzle under any circumstance. The resulting backpressure will distort flow rate measurements.
  • Do not over tighten the gauge or adapter into the brass gauge port. Always use a holdback.

Ordering Information
Gauge is ordered separately.
Click here for gauge selection information
Click here for list of gauges and to add to cart or quote

Spanner Wrenches Note: If you plan to use the Pitotless Nozzle with the new Little Hose Monster, no additional spanner wrenches are required. If you plan to connect to the HM2H or HM2HF, two spanner wrenches are needed to tighten/loosen the Pitotless Nozzle; The universal spanner wrench (WSPA) and the hole-type spanner wrench (WSPA104) used as a holdback on the body of the Pitotless Nozzle.

   
 

Toll Free: 888.202.9987
Phone: 847.434.0101
Fax: 847.434.0073

  © 2007 Hydro Flow Products, Inc - All Rights Reserved
503 West Golf Road, Arlington Heights, IL 60005
Designed by Advanced Horizons
Email